Checking GEM120CT Readings

Checking GEM120CT Readings

Overview

After installation, verify that the GEM120CT is reading correctly by comparing inverter data.

Verification Steps

  1. Switch off all PV generation (turn off PV breakers or disable via web portal).

  2. In the GivEnergy Portal, navigate to:

    Inverter → Remote Settings → Control → On/Off State → “Off / Auto Off”.

  3. Return to the Data tab and check readings:

Measurement

Expected Sign

Description

PAC

Negative (–)

Indicates import from grid

Load Power

Positive (+)

Indicates supply to load

If both values are equal in magnitude but opposite in sign, the CT orientation is correct.

Troubleshooting

Symptom

Cause

Fix

PAC shows positive during import

CT reversed

Re-orient clamp arrow toward load

No data on inverter

RS485 polarity reversed

Swap A/B wires

Irregular readings

CT wires extended

Replace with unmodified CT clamp


    • Related Articles

    • How to Install the GEM120CT Meter

      Overview This guide explains how to wire and mount the GEM120CT correctly to ensure accurate readings. Step-by-Step Installation Isolate power before working on the system. Mount the GEM120CT on a DIN rail in the distribution board. Connect voltage ...
    • How to Install the GEM630MCT Meter

      Overview Follow these steps to install and power the GEM630MCT safely and accurately. Step-by-Step Installation Isolate all power to the circuit before wiring. Mount the meter on a DIN rail inside the consumer unit or cabinet. Provide supply power (6 ...
    • GEM120CT Overview

      Every system will need at least 1 GEM120 (ID1) meter installing to monitor the import and export of the building. Every GEM120 meter needs a power supply/voltage reference point. This could be a dedicated supply from a 6A, for example. Every GEM120 ...
    • GEM120CT Quick Reference

      Function Port Cable Description CT + 1 White Connect to CT clamp white lead CT – 2 Black Connect to CT clamp black lead Neutral 3 Blue/Black Supply neutral Live 4 Brown/Red Supply live RS485 – 9 Green / White To inverter B– RS485 + 10 Orange / White ...
    • Monitor Your Meter from Portal

      Your GivEnergy system uses meter readings to calculate and display energy usage within the app and portal. These readings are generated by the inverter and depend on accurate meter installation and a stable internet connection. Data Calculation in ...