Version ZB040404 | 26-12-2025
- Certification update: DRM3 and DRM7 updated for AU to output reactive power.
- Fix: Optimise LoRa communications.
- Fix: Correct meter data power factor value.
- Fix: In parallel systems, load value previously reflected whole system instead of per inverter.
- Fix: EPS logic optimisation when switching from Island Mode to On-Grid.
- Fix: Optimise BMS error log data handling while in Off-Grid mode.
- New feature: Add support for generator control.
Version ZB030303 | 16-06-2025
- Optimise ECO mode to balance SOC during parallel operation.
- Resolve parallel BMS upgrade issue.
- Add backward compatibility for older SDM630 meters using FC 0x16.
- Optimise operation with inductive (high inrush) loads while in Island Mode.
- Add meter wiring detection function (see document: GIV-3HY-6~20K-HV Meter Wiring Detection Function SOP V1.0).
Version ZB020202 | 18-04-2025
- Optimise inverter power derating logic under high-temperature conditions.
- Start-up optimisation when both battery and PV are present: system boots on battery first, then engages PV.
- Update overload logic: three overloads in 5 seconds or five in 1 minute triggers fault; inverter waits 1 minute and self-recovers. Three faults within 1 hour disables self-recovery and raises “OCP Times Excessive”.
- Optimise fan self-test logic.
- Include externally monitored PV (ID2 & ID3) in total PV energy calculations.
- Parallel function optimisations.
- Optimise AFCI sensitivity.
- Improve parallel battery cluster calibration logic (requires BABA0007 or higher).
- Add RTCL “Safe Registers” for Grid Service functions to reduce excessive flash memory writes.
- Set default current limit to 100 A (disabled by default) with configurable range from 1–2000 A for commercial installations.
- Add Czech grid standards.
Version ZB010101 | 01-02-2025
- Initial factory release.